This site uses profiling cookies also from third parties, to send you targeted advertising messages and services in line with your preferences.
If you want to learn more or opt out of all or some cookies. click here
By continuing to browse, you consent to the use of cookies. The consent can also be expressed by clicking on the OK button or on the X key or continuing browsing, also by scrolling mode.
i-FX-W (1+i)-Y 1402 - 4652
Back
i-FX-W (1+i)-Y 1402 - 4652
High efficiency water cooled chiller
532 - 1784 kW
EUROPE
CEPED
50 Hz
Unit description
Single circuit indoor unit for the production of chilled water, with fixed speed and variable speed (Inverter Driven) screw compressors optimized for R134a, electronic expansion valve, high performing shell and tube condenser and shell and tube flooded evaporator, both designed and produced by Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A..
The resulting unit is extremely compact, thanks to the strategic layout, designed without base, frame and panels.
Versions
CA - High energy efficiency units
Features
HIGH EFFICIENCY Unit with high efficiency and reduced energy consumption, thanks to the inverter technology which contributes to lower operating costs and therefore a quick return on investment.
FLEXIBILITY Unit features a remarkable application flexibility thanks to the inverter technology which provides, taking into consideration the cooling capacity needed, the best cost/performance ratio and maximum efficiency.
TOTAL VERSATILITY The unit has been designed in a single circuit with one fixed speed compressor and one variable speed inverter compressor, in order to guarantee the best load efficiencies both at full and partial loads.
MAXIMUM COMPACTNESS Maximum compactness offers very high flexibility in the design process and installation operations, offering a premium solution in case of reduced clearances or when retrofitting existing installations.
AHRI CERTIFICATION Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI Directory at www.ahridirectory.org
Accessories
Touch Screen visual display
VPF (Variable Primary Flow) system
Set-up for remote connectivity with ModBus/Echelon protocol cards
Several devices for condensation control.
Controls
Controls
W3000TE The W3000TE controller offers advanced functions and algorithms. The large format keyboard provides a complete overview of the unit's status. The controls and the complete LCD display favor an easy and safe access to the unit's setup. These resources provide assessment and intervention of the unit, by means of a multi-level menu, with multiple languages available. The LED icons immediately show the circuit's operating status, as well as the fans and the water pumps (if present). The touch screen interface: 7.0” WVGA color display with adjustable LED back-light and front USB port is available as an option. The touch screen technology allows intuitive navigation between the various screens, safe access to the data with a three-level password protection as well as the graphic display of the performance of some monitored measurements.
The diagnostics are comprised of a complete alarm management system, with “black box” (via PC) and alarm log functions (via display or also PC) for a better analysis of the unit's performance.
For the systems made up of several units, the adjustment of the resources is performed by optional proprietary devices.
Consumption metering and performance measurement are possible as well. Supervision can be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet-over-IP, Echelon LonWorks, Bacnet MS/TP protocols.
Compatibility with the remote keyboard to manage up to 8 units.
The presence of the programmable timer allows for the creation of an operating profile containing up to 4 typical days and 10 time bands.
The control is characterized by the continuous modulation of the unit capacity, based on PID algorithms and referring to the water delivery temperature.
Optionally (VPF package), capacity modulation can be integrated with hydraulic flow modulation, thanks to inverter-driven pumps and to specific resources for the hydraulic circuit.